Hitachi

SJ700D Series(0.75kW-150kW), 3-phase 400V class Standard Specifications

Model SJ700D- European Version 007HFEF3 015HFEF3 022HFEF3 040HFEF3 055HFEF3 075HFEF3 110HFEF3 150HFEF3 185HFEF3 220HFEF3 300HFEF3 370HFEF3 450HFEF3 550HFEF3 750HFEF3 900HFEF3 1100HFEF3 1320/1500
HFEF3
Model SJ700D- US Version 007HFUF3 015HFUF3 022HFUF3 040HFUF3 055HFUF3 075HFUF3 110HFUF3 150HFUF3 185HFUF3 220HFUF3 300HFUF3 370HFUF3 450HFUF3 550HFUF3 750HFUF3 900HFUF3 1100HFUF3 1320/1500
HFUF3
Enclosure *1 IP20 IP20
Applicable motor (4-pole, kW(HP)) *2 CT *6 0.75(1) 1.5(2) 2.2(3) 4.0(5) 5.5(7.5) 7.5(10) 11(15) 15(20) 18.5(25) 22(30) 30(40) 37(50) 45(60) 55(75) 75(100) 90(120) 110(150) 132/150(175)
VT *6 1.5(2) 2.2(3) 3.7(5) 5.5(7.5) 7.5(10) 11(15) 15(20) 18.5(25) 22(30) 30(40) 37(50) 45(60) 55(75) 75(100) 90(125) 110(150) 132(175) 160(220)
Output Ratings Rated capacity
(KVA)
400V CT *6 1.7 2.6 3.6 6.2 9.7 13.1 17.3 22.1 26.3 33.2 40.1 51.9 62.3 76.2 103.2 121.9 150.3 180.1
VT *6 2.1 3.3 4.6 7.6 11.0 15.2 20.0 25.6 29.7 39.4 48.4 58.8 72.7 93.5 110.8 135 159.3 200.9
480V CT *6 2.0 3.1 4.3 7.4 11.6 15.8 20.7 26.6 31.5 39.9 48.2 62.3 74.8 91.4 123.8 146.3 180.4 216.1
VT *6 2.5 3.9 5.5 9.2 13.3 18.2 24.1 30.7 35.7 47.3 58.1 70.6 87.2 112.2 133 162.1 191.2 241.1
Rated output current (A) CT *6 2.5 3.8 5.3 9.0 14 19 25 32 38 48 58 75 91 112 149 176 217 260
VT *6 3.1 4.8 6.7 11.1 16 22 29 37 43 57 70 85 105 135 160 195 230 290
Overload capacity (output current) CT : 150%,60sec., 200%,3sec.
VT : 120%,60sec., 150%,5sec.
CT : 150%,60sec., 180%,3sec..
VT : 120%,60sec., 150%,5sec.
Rated output voltage *3 3-phase (3-wire) 380 to 480V (corresponding to input voltage)
Input Rating Rated input voltage (V) 3-phase (3-wire) 380 to 480V+10%, -15%, 50/60Hz±5%
Rated input current (A) CT *6 2.8 4.2 5.8 9.9 17 23 30 35 42 53 64 83 100 123 164 194 239 286
VT *6 4.3 5.9 8.1 13.3 20 24 32 41 47 63 77 94 116 149 176 199 253 300
Braking Dynamic braking (Short-time) *4 Built-in BRD circuit (optional resistor) External dynamic braking unit(option)
Minimum value of resistor (Ω) 100 100 100 70 70 35 35 24 24 20 —
Vibration *5 5.9m/s2(0.6G), 10~55Hz 2.9m/s2(0.3G), 10~55Hz
Integrated EMC filter Built-in (EN61800-3 category C3)
Zero-phase Reactor Built-in
Weight (lbs.) 3.5(7.7) 3.5(7.7) 3.5(7.7) 3.5(7.7) 6(13.2) 6(13.2) 6(13.2) 14(30.8) 14(30.8) 14(30.8) 22(48.4) 30(66) 30(66) 30(66) 55(121) 55(121) 70(154) 70(154)
*1
The protection method conforms to JIS C 0920(IEC60529).
*2
The applicable motor refers to Hitachi standard 3-phase motor(4-pole).
To use other motors, be sure to prevent the rated motor current (50Hz) from exceeding the rated output current of the inverter.
*3
The output voltage decreases as the main power supply voltage decreases except for the use of AVR function.
*4
Braking resistor is not integrated in the inverter. Please install optional braking resistor or dynamic braking unit when large braking torque is required.
*5
Conforms to the test method specified in JIS C 60068-2-6:2010(IEC 60068-2-6:2007).
*6
In case of driving light load application, be able to choose a low capacity inverter. CT and VT is the abbreviation of constant torque mode and variable torque mode.
© Hitachi, Ltd. 1994. All rights reserved.